A comprehensive fault location estimation using voltage sag profile for non-homogenous distribution networks

H. Mokhlis, H. Y. Li, Hasmaini Mohamad, A. H A Bakar

    Research output: Contribution to journalArticlepeer-review

    Abstract

    An improvement in service continuity of power supply in distribution system could be achieved through a fast fault location. In line with this objective, a fault location method for a distribution network is proposed in this paper. The method uses non-linear voltage sag profile equations as a means to locate a fault. Considering the possibility of having non-homogeneity of line impedances in distribution network, the voltage sag profile equations are constructed for each section. The possible fault location is estimated by incorporating the measured voltage magnitude and its corresponding phase angle into equation of voltage sag as a function of fault distance. The uncertainty of fault resistance is also considered in this method by constructing the voltage sag equations based on different fault resistance values. The performance of the algorithm is presented using an actual distribution network. © 2010 Praise Worthy Prize S.r.l. - All rights reserved.
    Original languageEnglish
    Pages (from-to)2310-2316
    Number of pages6
    JournalInternational Review of Electrical Engineering
    Volume5
    Issue number5
    Publication statusPublished - Sept 2010

    Keywords

    • Distribution network
    • Fault distance
    • Faulted section
    • Non-linear voltage sags

    Fingerprint

    Dive into the research topics of 'A comprehensive fault location estimation using voltage sag profile for non-homogenous distribution networks'. Together they form a unique fingerprint.