A new approach to inspect the internal pressure of vacuum switchgear

Li Wen Luo, Zi Yu Zhao, Hai Yu Li

    Research output: Contribution to journalArticlepeer-review

    Abstract

    A new approach is developed to inspect the internal pressure within the vacuum switchgear by no means of magnet-exciting coil, micro-discharge threshold voltage Ud and field emission threshold voltage Ue, all of which are available in laboratory. Experimental results show that internal pressure is a function of the ratio of the micro-discharge threshold voltage to the field emission threshold voltage i.e., Ud/Ue. By this method, the internal pressure in the range of 100-10-4 Pa within vacuum chambers can be inspected without magnet-exciting coil which is required in conventional magnetron discharge method.
    Original languageEnglish
    Pages (from-to)473-476
    Number of pages3
    JournalJournal of Shanghai Jiaotong University (Science)
    Volume13
    Issue number4
    DOIs
    Publication statusPublished - Aug 2008

    Keywords

    • Field emission
    • Internal pressure
    • Micro-discharge
    • Vacuum switchgear

    Fingerprint

    Dive into the research topics of 'A new approach to inspect the internal pressure of vacuum switchgear'. Together they form a unique fingerprint.

    Cite this