TY - JOUR
T1 - A novel voltage sag approach during unintentional islanding scenarios
T2 - A survey from real recorded events
AU - Serrano-Fontova, A.
AU - Casals-Torrens, Pau
AU - Bosch, Ricard
PY - 2019/7
Y1 - 2019/7
N2 - In this paper, a new voltage sag approach is analytically modelled and validated using both simulation and field measurements. The main aspect of this approach is to propose a new voltage sag feature which appears during unintentional islanding operations (IOs). The unintentional IO occurs when an induction motor is removed from the main utility following a circuit breaker (CB) clearing, transiently, the induction motors (IMs) are acting as generators maintaining the affected distribution feeder with voltage until it is reconnected. The voltage sag modelled in the current article follows an exponential form, as a matter of fact, here it will be demonstrated that the proposed model reaches satisfactorily the field measurements and evidences the dependability of the model adopted. Furthermore, it is worthwhile to note that this novel power quality (PQ) event has not been investigated yet and enhances voltage sag studies. Lastly, it is crucial to point out that all recorded events and a large amount of data needed so as to validate this transient, has been measured in a distribution network (DN) located in Spain. © 2019, European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ). All rights reserved.
AB - In this paper, a new voltage sag approach is analytically modelled and validated using both simulation and field measurements. The main aspect of this approach is to propose a new voltage sag feature which appears during unintentional islanding operations (IOs). The unintentional IO occurs when an induction motor is removed from the main utility following a circuit breaker (CB) clearing, transiently, the induction motors (IMs) are acting as generators maintaining the affected distribution feeder with voltage until it is reconnected. The voltage sag modelled in the current article follows an exponential form, as a matter of fact, here it will be demonstrated that the proposed model reaches satisfactorily the field measurements and evidences the dependability of the model adopted. Furthermore, it is worthwhile to note that this novel power quality (PQ) event has not been investigated yet and enhances voltage sag studies. Lastly, it is crucial to point out that all recorded events and a large amount of data needed so as to validate this transient, has been measured in a distribution network (DN) located in Spain. © 2019, European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ). All rights reserved.
KW - power quality
KW - islanding operations
KW - voltage sags
KW - distribution networks
UR - http://www.scopus.com/inward/record.url?eid=2-s2.0-85068793921&partnerID=MN8TOARS
U2 - 10.24084/repqj17.215
DO - 10.24084/repqj17.215
M3 - Article
SN - 2172-038X
SP - 43
EP - 48
JO - Renewable Energy and Power Quality Journal
JF - Renewable Energy and Power Quality Journal
IS - 17
ER -