Skip to main navigation Skip to search Skip to main content

Arcing faults detection on overhead lines from the voltage signals

  • K. J. Zoric
  • , M. B. Djuric
  • , V. V. Terzija

    Research output: Contribution to journal › Article › peer-review

    Abstract

    This paper presents a simple algorithm for arcing faults detection on overhead lines. The algorithm is based on the harmonic analysis of the bus voltage signals. It uses only the sine components of the odd higher harmonics of the bus voltage. Such an approach provides the algorithm with insensitivity to the cosine components of the bus voltage odd higher harmonics which can be generated by current odd cosine higher harmonics. The algorithm can be used for blocking the automatic reclosing of lines with permanent faults. A very simple arc model has been adopted. The algorithm was successfully tested with signals recorded on a real power system and signals obtained through computer simulated and laboratory tests. © 1997 Elsevier Science Ltd.
    Original languageEnglish
    Pages (from-to)299-303
    Number of pages4
    JournalInternational Journal of Electrical Power and Energy Systems
    Volume19
    Issue number5
    Publication statusPublished - Jun 1997

    Keywords

    • Autoreclosure
    • Fault arc
    • Power system protection

    Fingerprint

    Dive into the research topics of 'Arcing faults detection on overhead lines from the voltage signals'. Together they form a unique fingerprint.

    Cite this