Abstract
In this paper a new digital signal processing numerical algorithm for arcing faults detection and fault distance calculation is presented. It was derived by processing the line terminal voltages and currents. A simple square wave arc voltage model was assumed to represent the long arc in free air. The unknown model parameters (the line resistance and inductance, and arc voltage amplitude) were estimated by using Least Error Squares Technique. The new algorithm was successfully tested by computer simulated and laboratory tests.
Original language | English |
---|---|
Pages (from-to) | 49-59 |
Number of pages | 10 |
Journal | Advances in Modelling & Analysis. C: Systems Analysis, Control & Design |
Volume | 49 |
Issue number | 1 |
Publication status | Published - 1997 |