Generalized formulation of the optimal monitor placement problem for fault location

M. Avendaño-Mora, J. V. Milanović

    Research output: Contribution to journalArticlepeer-review

    Abstract

    This paper extends and generalizes the formulation of the optimal monitor placement problem for fault location for its implementation on large power systems. The proposed formulation, which models the monitor placement as an integer linear programming problem, is applied on several test systems including the IEEE reliability test system (RTS) and the IEEE 118-bus power flow test system. It was found that two monitors are sufficient in order to correctly locate any fault occurring throughout the RTS network. Studies on the 118-bus system revealed that full fault location observability can be achieved with 13 monitors. Simulation results from these studies show the applicability and effectiveness of the proposed modeling approach. © 2012 Elsevier B.V. All rights reserved.
    Original languageEnglish
    Pages (from-to)120-126
    Number of pages6
    JournalElectric Power Systems Research
    Volume93
    DOIs
    Publication statusPublished - Dec 2012

    Keywords

    • Fault location
    • Generalized formulation
    • Optimal monitor placement

    Fingerprint

    Dive into the research topics of 'Generalized formulation of the optimal monitor placement problem for fault location'. Together they form a unique fingerprint.

    Cite this