TY - JOUR
T1 - Identification of Weak Areas of Power Network Based on Exposure to Voltage Sags—Part I
T2 - Development of Sag Severity Index for Single-Event Characterization
AU - Liao, Huilian
AU - Abdelrahman, Sami
AU - Guo, Y.
AU - Milanovic, Jovica
PY - 2015
Y1 - 2015
N2 - This paper presents a new single-event characteristic, sag severity index (SSI), derived with respect to equipment sensitivity to voltage sags. It is more inclusive of associated uncertainties/variation in equipment response to voltage sags than existing single-event characteristics. By changing parameter settings, the index appropriately accounts for sag duration and adequately addresses the variation in equipment sensitivity. The value of the index changes continuously at the joining regions of different sag severity levels and reflects realistically the sensitivity trend of equipment embedded in voltage tolerance curves. The properties of the SSI are analyzed and discussed through comparison with characteristics of five previously reported single-event indices including four numerical indices and one fuzzy voltage sag index.
AB - This paper presents a new single-event characteristic, sag severity index (SSI), derived with respect to equipment sensitivity to voltage sags. It is more inclusive of associated uncertainties/variation in equipment response to voltage sags than existing single-event characteristics. By changing parameter settings, the index appropriately accounts for sag duration and adequately addresses the variation in equipment sensitivity. The value of the index changes continuously at the joining regions of different sag severity levels and reflects realistically the sensitivity trend of equipment embedded in voltage tolerance curves. The properties of the SSI are analyzed and discussed through comparison with characteristics of five previously reported single-event indices including four numerical indices and one fuzzy voltage sag index.
U2 - 10.1109/TPWRD.2014.2362965
DO - 10.1109/TPWRD.2014.2362965
M3 - Article
SN - 0885-8977
VL - 30
SP - 2392
EP - 2400
JO - I E E E Transactions on Power Delivery
JF - I E E E Transactions on Power Delivery
IS - 6
ER -