Abstract
The paper presents a methodology to identify generators at risk of subsynchronous resonance (SSR) in meshed AC/DC networks. Two risk indices are developed to rank generators based on the level of exposure to SSR. One of them measures the severity of subsynchronous torsional interactions, and the other indicates the gravity of transient torque problem. It is shown that proposed indices can be used to identify generators in the network that are at the risk of experiencing highmechanical torques due to SSR and to rank them based on severity of potential exposure to SSR. The methodology is demonstrated on meshed 16-machine, 68-bus IEEE test network with different series compensation levels of AC lines, asymmetrical compensation and voltage source converter (VSC) based HVDC lines. Finally, electromagnetic transient simulations are used to verify the ranking of generators obtained using developed oped indices. © 2013 IEEE.
Original language | English |
---|---|
Pages (from-to) | 4438-4447 |
Number of pages | 9 |
Journal | IEEE Transactions on Power Systems |
Volume | 28 |
Issue number | 4 |
DOIs | |
Publication status | Published - 2013 |
Keywords
- Frequency scan
- Series compensation
- Subsynchronous resonance (SSR)
- Torsional modes
- Voltage source converter (VSC) HVDC