Abstract
Currently there is no standard FRA interpretation methods and not all the FRA practitioners are capable to model transformer windings using equivalent circuits. A low-frequency transformer model of a three-limb core-type 1000 MVA 400/275/13 kV auto-transformer is established to analyze the effects of transformer electric parameters on the FRA plots. The equivalent electrical circuit of the magnetic core is derived based on the Principle of Duality. Air-core inductance and winding capacitances are included in the model. FRA simulation results are validated by measurement results, the suitability of transformer model is discussed and the dominant factors in different frequency regions are concluded through sensitivity studies.
Original language | English |
---|---|
Title of host publication | 2019 2nd International Conference on Electrical Materials and Power Equipment (ICEMPE) |
Pages | 592-595 |
DOIs | |
Publication status | E-pub ahead of print - 3 Jun 2019 |
Event | 2019 2nd International Conference on Electrical Materials and Power Equipment - Guangzhou, China Duration: 7 Apr 2019 → 10 Apr 2019 |
Conference
Conference | 2019 2nd International Conference on Electrical Materials and Power Equipment |
---|---|
Abbreviated title | ICEMPE |
Period | 7/04/19 → 10/04/19 |