Abstract
This paper presents an alternative fault location algorithm to estimate short-circuit faults location in electrical distribution networks using only voltage sags data. The proposed algorithm uses voltage sags profile as a means to locate fault. The possible fault locations is estimated by incorporating the measured voltage sags magnitude and its corresponding phase angle into an equation of voltage sag as a function of fault distance. A ranking procedure is also introduced to rank possible fault locations due the same electrical distance. The uncertainty of fault resistance is also considered in this algorithm. The performance of the technique is presented by testing it using an actual underground distribution network. The simulation results indicated a possibility of practical implementation. ©2010 IEEE.
Original language | English |
---|---|
Title of host publication | 2010 International Conference on Power System Technology: Technological Innovations Making Power Grid Smarter, POWERCON2010|Int. Conf. Power Syst. Technol.: Technol. Innovations Mak. Power Grid Smarter, POWERCON |
DOIs | |
Publication status | Published - 2010 |
Event | 2010 International Conference on Power System Technology: Technological Innovations Making Power Grid Smarter, POWERCON2010 - Hangzhou Duration: 1 Jul 2010 → … |
Conference
Conference | 2010 International Conference on Power System Technology: Technological Innovations Making Power Grid Smarter, POWERCON2010 |
---|---|
City | Hangzhou |
Period | 1/07/10 → … |
Keywords
- Distribution networks
- Fault location
- Phase shift
- Voltage magnitude