Multipurpose overhead lines protection numerical algorithm

Z. Radojevic, V. Terzija, M. Djuric

    Research output: Contribution to journalArticlepeer-review

    Abstract

    A numerical algorithm for multipurpose overhead lines protection, based on one terminal data and derived in the time domain, is presented. The fault location, direction and its nature (arcing or arcless fault) are estimated using the least squares error technique. The faulted phase voltage is modelled as a serial connection of fault resistance and arc voltage, offering more sophisticated line protection. The algorithm can be applied to both the ordinary and high-impedance fault detection, distance protection, intelligent autoreclosure, as well as for directional relaying. The new approach does not require the line zero-sequence resistance as an input datum. The algorithm is derived for the case of most frequent single-phase-to-ground asymmetrical faults. The results of algorithm testing through computer simulation are given. The influence of remote infeed, fault resistance, higher-order harmonics, power system frequency, network topology, line parameters and other factors are investigated and systematically presented.
    Original languageEnglish
    Pages (from-to)441-446
    Number of pages6
    JournalIET Research Journals - Generation Transmission & Distribution (formerly IEE Proceedings)
    Volume146
    Issue number5
    DOIs
    Publication statusPublished - Sept 1999

    Fingerprint

    Dive into the research topics of 'Multipurpose overhead lines protection numerical algorithm'. Together they form a unique fingerprint.