New parameter-free fault location algorithm for transmission lines in phasor domain

S. Padmanabhan, V. Terzija

    Research output: Chapter in Book/Conference proceedingConference contribution

    Abstract

    This paper presents a new fault location algorithm for transmission lines. It is different from other fault location algorithms since it does not require the use of any line parameters. Line parameter settings are only approximate and may vary with weather and loading condition. The settings-free aspect of the new algorithm makes it more reliable and accurate. All calculations are carried out in the phasor domain unlike many of the settings-free algorithms. The phasor domain approach in fault location offers an important advantage over the sequence domain approach as modifications can be made easily for lines where the sequence networks are coupled e.g. A series compensated line during fault. The algorithm uses synchronized data samples for voltage and currents from both ends of the line. © 2012 IEEE.
    Original languageEnglish
    Title of host publicationIEEE Power and Energy Society General Meeting|IEEE Power Energy Soc. Gen. Meet.
    DOIs
    Publication statusPublished - 2012
    Event2012 IEEE Power and Energy Society General Meeting, PES 2012 - San Diego, CA
    Duration: 1 Jul 2012 → …

    Conference

    Conference2012 IEEE Power and Energy Society General Meeting, PES 2012
    CitySan Diego, CA
    Period1/07/12 → …

    Keywords

    • Fault location
    • GPS synchronization
    • phasor domain
    • settings-free
    • transmission lines

    Fingerprint

    Dive into the research topics of 'New parameter-free fault location algorithm for transmission lines in phasor domain'. Together they form a unique fingerprint.