Abstract
Oil tests are crucial for condition assessment of transformers. Moisture, acidity, breakdown voltage, dissolved gas analysis and furans analysis are common oil tests carried out by utilities. {IEC} 60422 and {IEC} 60599 have specified some limit values for detecting any abnormalities based on oil tests. However, these limit values might not be suitable for all transformers at different ages or under different operating conditions and relying too much on these values could be costly for transformer utilities. Trend analysis of oil condition monitoring data is useful in providing additional information for the detection of any abnormalities of transformers. In this paper, analysis on the oil condition monitoring data of 132 {kV} distribution transformers is presented. Typical percentile values are calculated for moisture, acidity, breakdown voltage and furans levels whose results are compared with the limit values provided in {IEC} 60422 and {IEEE} C57.106. Trend analysis of moisture, acidity, furans, Carbon Monoxide ({CO}) and Carbon Dioxide ({CO}$_{\textrm{2}}$) are carried out on a transformer population. Acidity is found to be strongly related to transformer age and a model is proposed to represent ageing of transformers based on acidity.
| Original language | English |
|---|---|
| Title of host publication | Condition Monitoring and Diagnosis (CMD), 2012 International Conference on |
| Pages | 1156-1159 |
| Number of pages | 4 |
| DOIs | |
| Publication status | Published - 2012 |
Keywords
- acidity
- ageing byproducts and oil analysis
- Aging
- breakdown voltage
- carbon dioxide
- carbon monoxide
- condition assessment
- condition monitoring
- dissolved gas analysis
- distribution transformers
- electric breakdown
- furans analysis
- {IEC} 60422
- {IEC} 60599
- {IEC} standards
- {IEEE} C57.106
- in-service distribution transformers
- Market research
- moisture
- oil condition monitoring
- Oil insulation
- operational condition assessment
- power transformer insulation
- power transformers
- transformer age
- transformer population
- Transformers condition assessment
- transformer utilities
- voltage 132 kV