Power Flow in Four-Wire Distribution Networks - General Approach

Rade M. Ciric, A. Padilha Feltrin, Luis F. Ochoa

    Research output: Contribution to journalArticlepeer-review

    620 Downloads (Pure)

    Abstract

    The neutral wire in most power flow software is usually merged into phase wires using Kron's reduction. Since the neutral wire and the ground are not explicitly represented, neutral wire and ground currents and voltages remain unknown. In some applications, like power quality and safety analyses, loss analysis, etc., knowing the neutral wire and ground currents and voltages could be of special interest. In this paper, a general power flow algorithm for three-phase four-wire radial distribution networks, considering neutral grounding, based on backward-forward technique, is proposed. In this novel use of the technique, both the neutral wire and ground are explicitly represented. A problem of three-phase distribution system with earth return, as a special case of a four-wire network, is also elucidated. Results obtained from several case studies using medium- and low-voltage test feeders with unbalanced load, are presented and discussed.
    Original languageEnglish
    Pages (from-to)1283-1290
    Number of pages7
    JournalIEEE Transactions on Power Systems
    Volume18
    Issue number4
    DOIs
    Publication statusPublished - Nov 2003

    Keywords

    • Distribution networks
    • Earth return
    • Power flow
    • Three-phase four-wire
    • Unbalance

    Fingerprint

    Dive into the research topics of 'Power Flow in Four-Wire Distribution Networks - General Approach'. Together they form a unique fingerprint.

    Cite this