Surface analysis of asymmetrically aged 400 kV silicone rubber composite insulators

Y. Xiong, S. M. Rowland, J. Robertson, R. J. Day

    Research output: Contribution to journalArticlepeer-review

    216 Downloads (Pure)

    Abstract

    Surface analysis of 400 kV silicone rubber composite insulators is presented. These insulators have experienced 15 years of service on a coastal 400 kV transmission line. Inspection of the insulators shows low levels of degradation through cracking and oxidation of the surface. This has been quantified by microscopy, energy dispersive X-ray analysis (EDX), Fourier transform infrared spectroscopy (FTIR) and Raman spectroscopy. The analysis shows non-uniform ageing over each shed and ageing on the south side more advanced than on the north side. It is believed that non-uniform ageing was due to environmental factors including natural UV radiation and prevailing wind direction, and the resultant pattern of growth of organic species. EDX and FTIR were found to be the most useful and effective tools for analysis of these polymeric insulators. © 2008 IEEE.
    Original languageEnglish
    Article number4543114
    Pages (from-to)763-770
    Number of pages7
    JournalIEEE Transactions on Dielectrics and Electrical Insulation
    Volume15
    Issue number3
    DOIs
    Publication statusPublished - Jun 2008

    Keywords

    • Ageing
    • Composite
    • Insulators
    • Material analysis
    • NCI
    • Silicone rubber
    • Transmission line

    Fingerprint

    Dive into the research topics of 'Surface analysis of asymmetrically aged 400 kV silicone rubber composite insulators'. Together they form a unique fingerprint.