Abstract
As a potential insulation condition assessment technique for the field transformer, the correlation of the furan, or more specifically 2-furfural (2-FAL) measurement in oil and the insulating paper's degree of polymerization (DP) has been studied intensively in the laboratory by the means of accelerated ageing experiments. However due to the complicated operating conditions and design characteristics the field transformers are subjected to, it is not sensible to directly apply the correlation of 2FAL and DP derived based on laboratory works. In this paper, the field 2-FAL measurements have been analyzed on 49 UK National Grid (NG) field transmission power transformers. The insulating paper's DP of these transformers are estimated with the aid of the transformer thermal model, which was developed based on the thermal model in IEC transformer loading guide. As a result, a practical correlation has been established between the field 2-FAL measurement and insulating paper's DP estimates. The fitted model indicates that there is a possibility of developing a practical furan-DP relationship as a reliable insulation condition assessment technique for the field transformer. © 2012 IEEE.
Original language | English |
---|---|
Title of host publication | Proceedings of 2012 IEEE International Conference on Condition Monitoring and Diagnosis, CMD 2012|Proc. IEEE Int. Conf. Cond. Monit. Diagn., CMD |
Publisher | IEEE |
Pages | 521-524 |
Number of pages | 3 |
ISBN (Print) | 9781467310208 |
DOIs | |
Publication status | Published - 2012 |
Event | 2012 IEEE International Conference on Condition Monitoring and Diagnosis, CMD 2012 - Bali Duration: 1 Jul 2012 → … |
Conference
Conference | 2012 IEEE International Conference on Condition Monitoring and Diagnosis, CMD 2012 |
---|---|
City | Bali |
Period | 1/07/12 → … |
Keywords
- degree of polymerization
- furan diagnosis
- thermal modeling
- transmission power transformer